Product name |
RCD(RCCB) Type B |
Standards |
IEC61008-1/IEC62423:2009 |
Certificate |
CE, UKCA |
Electrical characteristics |
Number of poles |
2P/4P |
Rated frequency (Hz) |
50/60 |
Frame current (A)Inm |
63 |
Rated current (A)In |
40,63 |
Rated voltage (V) |
AC240V/415V (230V/400V) |
Rated insulation voltage (V)Ui |
500 |
Rated impulse withstand voltage (kV)Uimp |
4 |
Rated short-circuit breaking capacity (kA)Ics |
7.5 |
Rated short-circuit breaking capacity (kA)Icn |
10 |
Trip form |
Leakage trip |
Pollution level |
2 |
Rated residual action current (mA) |
30 |
Max. breaking time at the rated residual current |
0.1s |
Wave form of earth leakage sensed |
B |
Mechanical properties |
Electrical life |
6000 |
Mechanical life |
10000 |
Protection grade |
IP20 |
Indicator window |
Contact status indication |
Normal operation conditions and installation characteristics |
Storage temperature |
-35℃ ~ +70℃ |
Installation site altitude |
≤ 2000m |
Terminals |
Fixed with screw |
Maximum wiring capacity |
25mm2 |
Maximum limit torque Nm |
3.5 |
Installation category |
Class Ⅱ , Ⅲ |
Installation method |
35mm standard rail |
Incoming method |
Upper and lower |
RCD(RCCB) Type B should be installed on DIN rail terminal and can be connected to the wire less than 25mm2